国产精品成人777_欧美日韩一区二区超碰_18hdxxxx国产在线麻豆_亚洲精品动漫3d免费看_5月婷婷亚洲色图库_精品国产一区Aⅴ天美传媒_四虎国产精品免费观看_青青河边草免费观看电视_国产一级a爱做片777_少妇被粗大猛烈进出96

RC series 19-inch rack/tower high frequency online UPS 1 ~ 20kVA

Product profile

RC series 1~20kVA UPS with double conversion pure online architecture, the architecture can block the impact of abnormal power on the load, at the same time also can ensure the stable and reliable output, let the safe operation of the load, is the best can effectively solve the problem of all power architecture design, using digital control technology, to provide users with more secure power security.

Using 19 " rack design, it can provide a better power environment for the load, manifested in the voltage output range, frequency range, input noise filter, and zero conversion time between mains mode and battery mode. RC series with innovative software program control mode, not only reduces the volume, but also can greatly reduce the failure rate, effectively improve the safety and reliability of the use of power supply. Suitable for application in a variety of precision instrument systems, network systems, and important, or demanding power environment equipment.


Basic Features

1. 19'rack design to provide more flexible and reliable power protection for critical equipment.

2.?Real online design, output pure sine wave, pollution-free, conversion time is zero.

3. Intelligent MCU / DSP design, using PFC power factor correction, the input power factor is greater than 0.99, the whole machine efficiency is more than 93%, and the input current harmonic is less than 5%.

4.?Using high frequency and IGBT transformation technology, improve the efficiency and reliability of the whole machine, small volume, light weight.

5.?Perfect self-protection function, peak current and short circuit protection design, super load load impact resistance.

6.?Optional D class lightning protection device with surge prevention, lightning protection design, effectively protect the equipment from lightning interference.

7.?6 ~ 20 KVA can choose the parallel redundancy function to realize the N + 1 parallel redundancy.

8.?Intelligent local and remote monitoring function RS232 interface, compatible with SNMP.

9.?Tower and rack design, tower type and frame type free combination, more convenient installation.


Technical Specifications

Model

1K

1KS

2K

2KS

3K

3KS

6K

6KS

10K

10KS

3-10KS

3-15KS

3-20KS

Rated capacity?

(PF=0.9)

1kVA/0.9kW

2kVA/1.8kW

3kVA/2.7kW

6kVA/5.4kW

10kVA/9kW

15kVA/13.5kW

20kVA/18kW

Input

Voltage

120~300VAC (single-phase ? two-wire+G)/304~478VAC (three-phase four-wire+G)

Frequency

50/60Hz±10%

Output

Voltage

220/230±1%VAC

Frequency

Synchronized with input ? (mains mode), 50/60Hz±0.5%(battery mode)

Discharge waveform

Pure sine wave

Transfer time

Zero

Built-in battery (12V)

7/9Ahx2

-

7/9Ahx4

-

7/9Ahx6

-

7/9Ahx16

-

7/9Ahx16

-

-

External battery DC voltage (Vdc)

-

36

-

72

-

96

-

192

-

192

192/240

Battery type

Valve-controlled lead-acid ? maintenance-free storage battery

overload capacity

105-120%, after 10 seconds ? to the bypass;

120-140%,?after 200ms ? to the bypass;

140-150%,?after 200ms ? to the bypasss, then shutdown after 10 seconds;

>150%, ? shutdown?immediately?

The load peak ratio

3:?1(?max?)

Distortion rate (full load)

Linear load

<3%

Nonlinear loading

<5%

Communication interface

Rs 232 interface: optional USB interface) ? + SNMP ? smart slot

Working temperature

0C~40℃

Relative humidity

0%~90% (no condensation)

Size

? W×D×H

430×510×85mm(2U)

430×710×85mm(2U)

430×600×85mm(2U)

430×680×170mm(4U)

Standard type

2U

-

2U+2U

-

2U+2U

-

2U+2U

-

2U+2U

-

-

-

-

Extended time type

-

2U

-

2U

-

2U

-

2U

-

2U

2U

4U

4U

Reference weight (kg)

12/14

8.5

27/30

13

28/31

13.5

89

18

90

19

26

40

40

Compliance with standard

GB/T14715-2017; ? YD/T1095-2018; EN62040-1:2008+A1:2013; EN62040-2:2018